Testing & Tagging Services

Test and Tag

Testing & tagging is mandatory in Bendigo to protect your staff and the public and to adhere to occupational health and safety guidelines (AS/NZS 3760). The owner or manager of a premises or business has a legal and ethical obligation to your staff and clients to provide regular appliance test and tagging. For testing time frames please refer to table at the bottom of this page.

Exit & Emergency Light Testing

Testing of your Exit & Emergency Light System is mandatory under your states building, fire and essential services code. All scheduled maintenance testing must be carried out at least twice per annum.

At each inspection Electric Pro perform the following:

  1. Operate the exit and emergency lighting systems from their battery supply and ensure that they remain illuminated for at least 90 minutes
  2. Replace any defective lamps
  3. Replace any defective batteries with the correct type
  4. Clean all signs in accordance with Australian Standard Guidelines
  5. Advise those responsible for the operation of equipment of any changes or adjustments
  6. Ensure that the Maintenance and Log Manual has been filled out and left in a secure place

RCD Testing

A RCD (Residual Current Device) is a safety device that disconnects a circuit when it detects an imbalance of the electric current. The RCD turns the power off almost immediately to prevent electrocution. While you may still receive an electric shock, the duration will be very short, reducing the risk of serious injury.

Electric Pro will inspect and test your workplace Fixed and Portable RCD’s in accordance with AS/NZS 3760:2010 and state based legislation.  A simple Operating Time Test will be conducted to ensure your RCD trips the power within the recommended time frame. You will then receive a copy of all test results.

Type of Environment and/or EquipmentInterval Between Inspection and Tests for Appliance Test TagCord Extension Sets and EPODs
Class of EquipmentResidual Current Devices (RCDs)
Class 1 – protectively earthed equipmentClass 2 – double insulated equipmentPush-button test by userOperating Time test
PortableFixedPortableFixed
Factories, workshops, places of work or repair, manufacturing, assembly, maintenance or fabrication6 months12 monthsDaily or before every use6 months12 months12 months6 months
Laboratories, healthcare and educational establishments, tea rooms and office kitchens12 months12 months3 months or before every use6 months2 years2 years12 months
Office environment: When the equipment or supply flexible cord is subject to flexing in normal use OR is open to abuse OR is in a hostile environment12 months12 months3 months6 months2 years2 years12 months
Office environment: When the equipment or supply flexible cord is NOT subject to flexing in normal use and is NOT open to abuse and is NOT in a hostile environment5 years5 years3 months6 months2 years2 years5 years
Hire equipmentInspect before each hire, test monthlyInspect before each hire, test monthlyPrior to each hire or monthlyN/APrior to each hire or monthlyN/AInspect before each hire, test monthly
Repaired/serviced/second hand equipmentAfter repair or service which could affect electrical safety or on introduction to service
Equipment used for commercial cleaning6 months12 months3 monthsN/A2 yearsN/A6 months
Residential2 years2 years6 months6 months2 years2 years2 years

Interested in learning more about our Testing & Tagging options? Get in touch with us today.